A camera that works on a bench and then flickers, reboots or loses its infrared at night is often fed through a cable that is too thin for the distance. The cause is voltage drop, and it can be calculated with a school level formula. This guide shows the calculation for a 12 V camera on a 50 metre run, and explains why the answer matters more at night.
Key Engineering Takeaways
- Voltage drop equals current multiplied by the resistance of both the outgoing and the return conductor.
- Copper resistance per metre is about 0.0172 divided by the cross section area in square millimetres.
- Cameras draw more current at night when infrared lamps switch on, so check the worst case.
- Keep total drop under about 5 percent of the supply voltage, and always read the camera datasheet for its allowed range.
The formula
The resistance of a copper conductor is its resistivity multiplied by length and divided by cross section. For copper at room temperature the resistivity is about 0.0172 ohm square millimetre per metre. A 1 square millimetre conductor therefore has about 0.0172 ohm per metre.
Power flows out along one conductor and returns along the other, so the length that counts is twice the cable run. Voltage drop is then current multiplied by that total resistance.
Worked example: 50 metres, 0.5 ampere
A 12 V bullet camera with infrared lamps draws 0.5 A at night, which is 6 W. The cable run is 50 m, so conductor length is 100 m.
With a 0.5 square millimetre conductor, resistance per metre is 0.0172 / 0.5 = 0.0344 ohm, and 100 m gives 3.44 ohm. Voltage drop is 0.5 x 3.44 = 1.72 V, or 14 percent of 12 V. The camera receives only 10.3 V and is likely to misbehave.
With 1.0 square millimetre, resistance is 1.72 ohm and the drop is 0.86 V, or 7.2 percent. With 1.5 square millimetre, resistance is 1.15 ohm and the drop is 0.57 V, or 4.8 percent. Only the 1.5 square millimetre cable passes the 5 percent guideline.
Options when the drop is too high
You have four ways to fix a long run. Use thicker cable. Move the power supply closer to the camera, which is usually possible when several cameras sit in one area. Raise the supply voltage, since a 24 V AC or DC camera tolerates a larger drop. Or avoid the problem by powering the camera over Ethernet, which delivers power at 48 V and carries data on the same cable up to 100 metres.
For a new project with IP cameras, PoE is almost always the better answer, because the voltage is high enough that drop is rarely an issue within the length limit.
Practical installation notes
- Check the datasheet for the supply voltage range, for example 12 V plus or minus 10 percent.
- Measure voltage at the camera with the infrared lamps on, not in daylight.
- Use proper connectors and avoid twisted and taped joints, which add resistance and fail in the rain.
- Keep power cables away from heavy power lines to limit interference, and earth equipment according to the site design.
- Label every cable at both ends so a faulty run can be found without opening ducts.
Conclusion & Next Steps
Voltage drop is simple to calculate and costly to ignore, because the fault appears only at night and in the longest runs. Write the cable size, the length and the expected drop in the design drawing for every camera, and test with a meter at handover. We record those readings in the commissioning report.