Every electric lock has a default state when power is lost. Some open and some stay locked. The choice is one of the most important decisions in an access control design, because it decides whether people can leave a building in an emergency and whether a thief can walk into a store room during a power cut. It is also easy to get wrong when locks are chosen from a catalogue.
Key Engineering Takeaways
- A fail safe lock unlocks when power is lost. A fail secure lock stays locked.
- Doors on escape routes must release for people leaving, and the fire authority and the building design decide how.
- Magnetic locks are fail safe and draw current all the time. Electric strikes are usually fail secure and draw current only when releasing.
- Size the power supply from the total current of locks, readers and controllers, and size the battery for the backup time you need.
The two behaviours
A fail safe lock needs power to stay locked. When the supply fails, it releases. A magnetic lock works this way, because the magnet holds the door shut only while current flows. A fail secure lock needs power to unlock. A typical electric strike stays locked in a power cut but can still be opened from the inside with the handle, and from the outside with a mechanical key if one is fitted.
Neither is better. Each suits a different door.
Choosing by door
Doors on the way out of a building must never trap people. For these doors, the usual design is a fail safe lock with a request to exit button, a manual release at the door and a link to the fire alarm panel so that the lock releases when the alarm operates. The exact requirement comes from the building regulations and the fire authority, so confirm it for your site.
Doors that protect assets, such as a server room, a pharmacy or a cash room, are often fail secure with a mechanical override and a free exit by handle. In a power failure the room stays secure, and someone inside can always leave.
- Main entrance and stair doors: fail safe, linked to the fire alarm.
- Server and store rooms: fail secure, free exit from inside.
- Offices: either, depending on whether the room is an escape route.
- Doors leading to hazardous areas: decide with the safety team, and record the decision.
Worked example: power supply for 12 magnetic locks
A site has 12 doors fitted with 12 V magnetic locks. Each lock draws about 0.5 A continuously, so the locks need 12 x 0.5 = 6 A. Twelve readers draw about 0.15 A each, which is 1.8 A. The controller and the exit buttons take about 0.5 A. The total is 6 + 1.8 + 0.5 = 8.3 A.
Add a 25 percent margin so the supply is not at its limit and can feed one more door later: 8.3 x 1.25 = 10.4 A. A 12 A power supply is the next common size.
Now the battery. If the doors must stay locked for 4 hours in an outage, the battery must supply 8.3 A for 4 hours, which is 33.2 Ah. Allow 80 percent usable depth of discharge: 33.2 / 0.8 = 41.5 Ah. A 12 V battery of about 42 Ah is needed, and a larger one if you want more margin. Magnetic locks use the most power, which is one reason strikes are used where continuous holding is not needed.
Other details that matter
- Cable size: long runs to locks lose voltage, as with cameras, so check the drop at the lock.
- Door closers and frames: a lock that does not meet its frame will not hold, whatever the controller does.
- Fire alarm link: use a relay from the fire panel that cuts lock power, and test it at commissioning.
- Audit trail: the controller log shows who opened a door and when, and is useful after an incident.
- Maintenance: test the release, the battery and the alarm link at set intervals and record the results.
Conclusion & Next Steps
A door schedule is the best tool for this work. It lists each door, its purpose, whether it is an escape route, the lock type, the failure mode and the power load. Review it with the fire authority, the building owner and the security team before anything is ordered. We prepare the schedule as part of the design and we test every release at handover.